海信日立401DHVM-64D1變頻壓縮機使用條件范圍 Operating Conditions
使用冷媒 Refrigerant R407C
排氣溫度 Discharge Temp.
(冷凝溫度+15℃)~120℃以下
(Condensing Temp.+15℃)~120℃ Max.
電機繞組溫度 Winding Temp. 120℃以下 120℃Max.
供油溫度 Oil Temp.
(冷凝溫度+10℃)~120℃以下
(Condensing Temp.+10℃)~120℃ Max.
運轉電壓 Running Voltage
額定電壓的±10%(壓縮機端子間的電壓)
Within 10% of the rating at compressor terminal
平衡起動 Balance At Starting
15kg/cm2G 以下起動,起動次數在10 次/小時以下
15kg/cm2G Max.,10 Times Max. within 1 hour.
排氣壓力2.5kg/cm2G 以下,起動10 次/小時以下(排氣側設有
逆止閥、供油配管設有電磁閥)
D.P. 2.5kg/cm2G Max., 10 Times Max. within 1 hour.(One
Way Valve & Solenoid Valve installed)
起動時的壓力差
Pressure Difference At Starting
排氣壓力20kg/cm2G 以下,排氣和吸入壓差在13kg/cm2G 以下,
起動10 次/小時以下(排氣側無逆止閥、供油配管無電磁閥)
D.P. 20kg/cm2G Max.,D.P.-S.P. less than 13kg/cm2G, 10
Times Max. within 1 hour.(NO One Way Valve & Solenoid
Valve)
起動時的壓力差(變頻壓縮機)
Pressure Difference At Starting
(Inverter Controlled Compressors)
排氣壓力20kg/cm2G 以下,排氣和吸入壓差在7kg/cm2G 以下,
起動10 次/小時以下
D.P. 20kg/cm2G Max.,D.P.-S.P. less than 7kg/cm2G, 10
Times Max. within 1 hour.
配管(銅管)應力
Copper Piping Stress
啟動時:50MPa 以下 Start:50MPa Max.
運轉時:10MPa 以下 Run:10MPa Max.
冷媒水分含量Refrigerant Moisture Level 60ppm 以下 60ppm Max.
系統固體雜質含量Solid Impurities Level 100mg 以下 100mg Max.
運轉傾斜角度 Tilt In Operation 壓縮機傾斜較大5°以內 5 deg. Max.
G401DHVM-64D1
3
※ 海信日立壓縮機401DHVM-64D1其他注意事項 Remarks:
1.制冷系統 The refrigeration system
1)潤滑油與冷媒的重量比(潤滑油/冷媒)應在0.4 以上;
The ratio of oil to the refrigerant (oil/refrigerant) should be higher than 0.4 in weight basis.
2)當系統中壓縮機存在液態冷媒回流情況時,應采用儲液罐等設計避免液態冷媒回流;
When the compressor in the system has the liquid refrigerant flooding back operation,the
accumulator is required.
3)向壓縮機充油或冷媒時,必須從排氣側進行;
Charge oil or refrigerant from the discharge pipe.
4)系統應設置高壓壓力開關,參考設定值為2.8±0.1MPa。
Using high pressure switch in the refrigeration system is required,we advise setting pressure
as follow: 2.8±0.1MPa,
2.壓縮機在去除吸、排氣接頭蓋后,請勿放置10 分鐘以上;
Installation shall be completed within 10 minutes after removing the caps of suction and discharge
tube.
3.請勿壓縮空氣;
Do not compress air.
4.在真空狀態下請勿通電;
Do not energize under vacuumed condition.
5.熱泵系統必須在壓縮機底部安裝油加熱器(40~80W,220V);
Crankcase heater is required if the refrigeration system is heat pump.
6.運轉時,各相間的電壓偏差應在額定電壓的3%以內;
Voltage (run):Voltage deviation each phase shall be within 3% of the rated voltage.
7.請勿反向旋轉;
Do not reverse rotate.
8.壓縮機的接地裝置應*與制冷器具的接地裝置連接;
The compressor’s ground should be connected with that of refrigeration system permanently and
firmly.
9.成箱壓縮機包裝件的疊放堆碼極限為2 箱,裝卸過程中嚴禁翻滾。
Pile limits 2 pallet.Tumbling is forbidden during handling.